What Is an Evacuation Diagram?

What an evacuation diagram is, what it must show under AS 3745, how to read one, how it differs from an evacuation or emergency plan, who is responsible, and how long it's valid — with a real labelled example.

Published 15 November 2026

Last updated 15 November 2026

Reviewed by Fadi Raslan, licensed technician (TTT69067)

An evacuation diagram is a floor plan mounted on the wall of a building that shows you where you are, the way out, the exits, the fire equipment and the emergency assembly area. In Australia, evacuation diagrams are prepared to AS 3745-2010, Planning for emergencies in facilities (clause 3.5), and they form part of the emergency plan that every NSW workplace must have under section 43 of the Work Health and Safety Regulation 2025.

People also call them evacuation plans, fire evacuation plans, fire escape plans or evacuation maps. (A fire block plan is something different — see below.) Below: what a compliant diagram must show (with a real example), how to read one, who is responsible for it, and how long it stays valid.

What does an evacuation diagram look like?

Here is a real evacuation diagram we prepared for a Sydney medical centre (details anonymised). Every compliant diagram has the same building blocks:

Sample evacuation diagram with You Are Here marker, exits, fire equipment and assembly area labelled
Sample evacuation diagram — a medical centre example (details anonymised). Click the image to view it at full size.
  1. 1The title "EVACUATION DIAGRAM" — so it's recognised instantly.
  2. 2"You Are Here" — a marker at the exact spot where the diagram hangs.
  3. 3The floor plan — a pictorial representation of the floor or area, drawn to suit the reader's viewpoint.
  4. 4Designated exits — shown in green, with the paths of travel to reach them.
  5. 5Fire equipment — extinguishers, fire blankets, hose reels and hydrants, shown in red.
  6. 6Communication equipment — manual call points and emergency warning panels, where present.
  7. 7The emergency assembly area — where everyone gathers once outside.
  8. 8A legend — explaining every symbol used.
  9. 9Site address and validity date — so anyone can confirm the diagram belongs to this building and is still current.

What must an evacuation diagram show under AS 3745?

AS 3745-2010 separates minimum elements (always required) from optional elements (added where useful). Amendment 2 (2018) made the facility address and paths of travel mandatory.

Minimum elements (required)Optional elements (where useful)
Title "Evacuation Diagram"Direction of opening doors
"You Are Here" locationFire indicator panel
Designated exitsFirst aid kits and AED locations
Paths of travel to exitsSpill kits
Fire equipment (extinguishers, blankets, hose reels, hydrants)Fire and smoke doors
Communication equipment (manual call points, EWIS)"Do not use lifts in an emergency"
Assembly areaEmergency steps (e.g. "Call 000")
LegendNorth point
Facility address and validity dateElectrical switchboard location
Correct orientation to the viewer

For a full compliance checklist — and what to do when a diagram has expired — see our evacuation diagram requirements guide.

Evacuation diagram vs evacuation plan vs emergency plan

These terms get mixed up constantly. Here's the difference:

TermWhat it isWhere it lives
Evacuation diagramThe wall-mounted floor plan showing "You Are Here", exits, fire equipment and the assembly area (AS 3745 clause 3.5)On the wall, at each nominated location
Evacuation plan / fire evacuation plan / fire escape plan / evacuation mapEveryday names for the evacuation diagramSame as above
Fire block planA whole-building or site plan for emergency services and wardens, often kept at the fire indicator panelAt the fire panel or main entry
Emergency planThe written document setting out emergency procedures, roles (wardens) and the emergency control organisation — the diagrams are part of itIn your emergency management manual

In short: the emergency plan is the rulebook; the evacuation diagram is the map on the wall that puts it into practice.

How do you read an evacuation diagram?

  1. 1Find "You Are Here". That's your position — the diagram hanging in front of you.
  2. 2Check the orientation. A compliant diagram is drawn so that what you are facing is at the top, and left on the diagram is left in real life. You shouldn't have to turn the map in your head.
  3. 3Follow the green path from "You Are Here" to the nearest exit, and note the alternative exit in case the first is blocked.
  4. 4Note the assembly area you'll head to once outside, and the fire equipment you pass on the way.

Orientation is the most common failure we see. A north-up diagram copied onto every wall will point people the wrong way on any wall that doesn't face north — which is why AS 3745 requires each diagram to show the direction from where it's displayed to the exit. Every diagram we prepare is rotated to its exact mounting position.

Are evacuation diagrams required by law in NSW?

Under section 43 of the NSW Work Health and Safety Regulation 2025, a person conducting a business or undertaking must prepare, maintain and implement an emergency plan that includes evacuation procedures. The Regulation doesn't name evacuation diagrams or AS 3745 — but diagrams are the accepted way to show evacuation procedures, and AS 3745-2010 is the recognised Australian Standard for them.

Some settings have their own explicit rules. Childcare and early learning services, for example, must display an emergency and evacuation floor plan near each exit under regulation 97 of the Education and Care Services National Regulations — see our childcare evacuation diagram guide. Your building may also have fire-safety requirements of its own, so check with your building manager or certifier.

Who is responsible for evacuation diagrams?

SituationUsually responsible
A business in its own premisesThe business (the PCBU), as part of its emergency plan
A tenant in a shared buildingThe tenant for its own tenancy; the building owner or manager for common areas and the overall building plan
Strata buildingsThe owners corporation for common property — see fire safety for strata buildings
Childcare and early learning servicesThe approved provider (regulation 97)

The number and location of diagrams is decided by your emergency planning committee or building manager. We advise on placement, but the person accountable for the site signs off.

What size should an evacuation diagram be, and where should it go?

RequirementAS 3745 guidance
Size — minimum elements onlyAt least A4, with the floor plan at least 200 × 150 mm
Size — minimum + optional elementsAt least A3, with the floor plan at least 300 × 200 mm
Mounting heightTop of the diagram 1.2–1.6 m above the floor
WhereWhere occupants and visitors can see it — typically beside the door or near fire equipment
NeverOn a fire door or smoke door

How long is an evacuation diagram valid?

Every evacuation diagram carries a validity date. Review it at least every five years, and straight away whenever the layout, exits, fire equipment or assembly area changes — whichever comes first. NSW Education's guidance for services is to renew the validity date after each review even if nothing on the diagram changed. An out-of-date diagram is one of the most common findings in fire-safety audits.

Common evacuation diagram mistakes

  • ✓North-up on every wall — points readers the wrong way.
  • ✓Expired validity dates, or no date at all.
  • ✓Not updated after a fit-out — exits or equipment moved, diagram didn't.
  • ✓Mounted on fire or smoke doors.
  • ✓One generic diagram copied across rooms or floors — the "You Are Here" and orientation must suit each location.
  • ✓Missing the address or paths of travel — both mandatory since Amendment 2.

How to get or update your evacuation diagrams

We prepare evacuation diagrams in line with AS 3745-2010, two ways:

  • ✓Remote, Australia-wide — send your floor plan or existing/expired diagram and we return a print-ready PDF with a new validity date in about 2 business days, from $70 + GST per diagram. Because we work from the information you supply, please confirm it reflects your current site before mounting.
  • ✓On-site, Sydney and NSW — we survey every mounting point, design correctly oriented diagrams, then print, frame and install. By quote.

See our evacuation diagram service. In Sydney, we can check your fire extinguishers and exit lighting in the same visit.

Need evacuation diagrams prepared or updated? See our evacuation diagram service — remote Australia-wide from $70 + GST per diagram, or on-site across Sydney and NSW by quote.

Frequently Asked Questions

What is an evacuation diagram?

An evacuation diagram is a floor plan mounted on the wall of a building that shows where you are, the way out, the exits, fire equipment and the emergency assembly area. In Australia they are prepared to AS 3745-2010 and form part of a workplace's emergency plan.

Is an evacuation diagram the same as an evacuation plan?

In everyday use, yes — "evacuation plan", "fire evacuation plan" and "evacuation map" usually mean the wall-mounted evacuation diagram. Technically, the emergency plan is the written document of procedures and roles, and the evacuation diagram is the map that forms part of it.

What must be on an evacuation diagram?

Under AS 3745-2010 the minimum elements are the title, a "You Are Here" marker, designated exits and paths of travel, fire equipment, communication equipment, the assembly area, a legend, the facility address and a validity date — and the diagram must be oriented to the viewer.

Are evacuation diagrams a legal requirement in NSW?

NSW businesses must have an emergency plan that covers evacuation procedures under section 43 of the Work Health and Safety Regulation 2025. The Regulation doesn't name evacuation diagrams, but they are the accepted way to show evacuation procedures, and AS 3745-2010 is the recognised standard. Childcare services have an explicit requirement under regulation 97.

How long is an evacuation diagram valid?

Review it at least every five years, or immediately when the layout, exits, fire equipment or assembly area changes — whichever comes first — and renew the validity date after each review.

Which way should an evacuation diagram face?

It should be drawn so that the direction the reader is facing is at the top of the diagram, with left on the map matching left in real life. A north-up diagram is only correct on a wall where the reader faces north.

What is the difference between a fire block plan and an evacuation diagram?

A fire block plan is a whole-building plan for emergency services and wardens, usually kept at the fire indicator panel. An evacuation diagram is the occupant-facing map at each nominated location, showing "You Are Here" and the way out.

Who is responsible for evacuation diagrams?

The business running the workplace is responsible as part of its emergency plan. In shared buildings the building owner or manager handles common areas, in strata buildings the owners corporation is responsible for common property, and in childcare services it is the approved provider.